Title of article
Comparison of R407C and R417A heat transfer coefficients and pressure drops during flow boiling in a horizontal smooth tube
Author/Authors
Aprea، نويسنده , , C. and Greco، نويسنده , , A. and Rosato، نويسنده , , A.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2008
Pages
8
From page
1629
To page
1636
Abstract
The sizing of evaporators for refrigeration and air conditioning applications is essential for good cycle performance. For this reason, accurate knowledge of the heat transfer coefficients and pressures drops of refrigerants is mandatory. In order to identify the best substitute for R22, in this paper, the experimental local heat transfer coefficients and pressure drops during flow boiling of R407C and R417A were compared.
st section was a smooth, horizontal, stainless steel tube (6.0 mm I.D., 8.0 mm O.D., 6.0 m length) uniformly heated by the Joule effect. The experimental tests were conducted by varying the evaporating pressures within the range from 3.6 to 10.3 bar, heat fluxes within the range from 7.6 to 28.5 kW/m2 and refrigerant mass fluxes within the range from 195 to 706 kg/m2 s.
Keywords
Pressure drops , Evaporation , R417A , R407C , Heat transfer coefficients
Journal title
Energy Conversion and Management
Serial Year
2008
Journal title
Energy Conversion and Management
Record number
2333896
Link To Document