Title of article :
Comparison between the energy performance of a ground coupled water to water heat pump system and an air to water heat pump system for heating and cooling in typical conditions of the European Mediterranean coast
Author/Authors :
Urchueguيa، نويسنده , , J.F. and Zacarés، نويسنده , , M. and Corberلn، نويسنده , , J.M. Sanchez-Montero، نويسنده , , ء. and Martos، نويسنده , , J. and Witte، نويسنده , , H.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Abstract :
The investigation presented in this article was aimed at demonstrating the technical and economical feasibility of using ground source heat pump systems in mixed climate applications, where cooling requirements are dominant. We show an experimental comparison between a ground coupled heat pump system and a conventional air to water heat pump system, focussing at the heating and cooling energy performance. A direct comparison could be made as both systems are linked, in parallel, to the same building with exactly the same loads and climatic conditions. For a whole climatic season the results obtained show that the geothermal system saves, in terms of primary energy consumption, a 43 ± 17 % of the energy consumed by the conventional one when the system is working in heating mode, and a 37 ± 18 % when the system is working in cooling mode.
Keywords :
Ground coupled (geothermal) heat pumps , Heating and cooling systems , Energy efficiency , Heat pumps
Journal title :
Energy Conversion and Management
Journal title :
Energy Conversion and Management