Title of article
A novel approach to determine the interphase transformer inductance of 18 pulse rectifiers
Author/Authors
Sefa، نويسنده , , Ibrahim and Altin، نويسنده , , Necmi، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2009
Pages
9
From page
2495
To page
2503
Abstract
The interphase transformer inductance seriously affects the performance of 18 pulse rectifiers. Low inductance values cause non-characteristic harmonics whereas high inductance values increase the rectifier cost and size. Hence, determination of the interphase transformer inductance value is an important problem in the design of 18 pulse rectifiers. In this paper, an approach to determine the optimum inductance value of an interphase transformer is proposed and a practical formula is introduced. The proposed approach has been validated with simulation and experimental studies carried out with designed capacitive loaded autotransformer based 18 pulse rectifier for different IPT inductance values at different load levels. Experimental and simulation results show that cost effective interphase transformer inductance value can be determined with the proposed approach and this value reduces the line current harmonics and improves power factor drastically.
Keywords
total harmonic distortion , Rectifier harmonics , 18 pulse rectifiers , Interphase transformer
Journal title
Energy Conversion and Management
Serial Year
2009
Journal title
Energy Conversion and Management
Record number
2334875