Title of article :
Experimental study of hydronic panels system and its environment
Author/Authors :
Dيaz، نويسنده , , Néstor Fonseca، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
11
From page :
770
To page :
780
Abstract :
An experimental analysis of hydronic cooling or heating ceiling panels coupled to the building is present in this investigation as a part of the commissioning study of this system. Two test chambers are adapted in a way to reproduce the interaction of the system to the building (windows, internal thermal loads distribution, building structure and ventilation). A series of experimental tests were performed in which the main objective is to observe the influence of parameters such as the water mass flow rate, supply water temperature, thermal load distribution, window and ventilation system effects on the hydronic ceiling capacity and comfort conditions. Test results show that the influence of asymmetric surfaces temperatures inside the room, especially the window effect is not negligible. Then, it is clear that the cooling hydronic ceiling must be evaluated coupled to the building systems and structure.
Keywords :
radiation , Experimental , Building , Hydronic panels
Journal title :
Energy Conversion and Management
Serial Year :
2011
Journal title :
Energy Conversion and Management
Record number :
2335435
Link To Document :
بازگشت