Title of article
Numerical analysis of 3D cross flow between corrugated parallel plates in evaporative coolers
Author/Authors
Tavakoli، نويسنده , , Ehsan and Hosseini، نويسنده , , Reza، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2011
Pages
9
From page
884
To page
892
Abstract
Steady state laminar 3D cross flow, between two sinusoidal corrugated parallel plates, with perpendicular directions of corrugation is modeled in the present work. The velocity field is assumed to be periodic across each wave but the thermal field is assumed to be developing. The results are studied as thermal development and effect of the number of waves along the flow direction on bulk temperature and saturation efficiency, due to different Reynolds numbers, when Prandtl number is 0.7. Saturation efficiency increases with increase in the number of waves along media depth, and decreases when Reynolds number or the amplitude to wavelength ratio grows. There is a specific length of media depth in each geometrical aspect ratio and Reynolds number, which can satisfy any specific saturation efficiency. With respect to relations between desired relative humidity and saturation efficiency, in different residential, agricultural or industrial applications, the proper size of the domain or Reynolds number, can be estimated through the resulted diagrams. Respectively, further number of waves along media, follows unwanted additional pressure drop and waste of energy and material.
Keywords
Wavy , Evaporative cooling , Saturation efficiency , thermally developing
Journal title
Energy Conversion and Management
Serial Year
2011
Journal title
Energy Conversion and Management
Record number
2335458
Link To Document