Title of article :
Investigating the performance of cellulosic evaporative cooling pads
Author/Authors :
Malli، نويسنده , , Abdollah and Seyf، نويسنده , , Hamid Reza and Layeghi، نويسنده , , Mohammad and Sharifian، نويسنده , , Seyedmehdi and Behravesh، نويسنده , , Hamid، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Abstract :
In the present work, thermal performance of two types of cellulosic pads (5090 and 7090) which were made from corrugated papers has been studied experimentally. Samples were tested in a sub sonic wind tunnel made from polyethylene. The pads areas are 0.5 × 0.5 m2 with 75, 100 and 150 mm thicknesses. Pressure drop, humidity variation, evaporated water and effectiveness have been investigated for several inlet air velocities. The results show that overall pressure drop and amount of evaporated water increase by increasing the inlet air velocity and thickness in both types of pads. On the other hand, effectiveness and humidity variation decrease by increasing inlet air velocity.
Keywords :
Corrugated papers , Evaporative cooler , Evaporative cooling pads
Journal title :
Energy Conversion and Management
Journal title :
Energy Conversion and Management