• Title of article

    Actual performance and characteristic of a grid connected photovoltaic power system in the tropics: A short term evaluation

  • Author/Authors

    Khatib، نويسنده , , Tamer and Sopian، نويسنده , , Kamaruzzaman and Kazem، نويسنده , , Hussein A.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2013
  • Pages
    5
  • From page
    115
  • To page
    119
  • Abstract
    This paper presents a field operation experience for a grid connected PV system under tropical climate. The system is consisted of a 5 kWp photovoltaic (PV) array and a 6 kW DC/AC inverter. The operation performance data are recorded in order to develop accurate mathematical models for the system as well as to evaluate the productivity of the system. The experiment results show that, the average PV performance (the ratio of the theoretical performance to the actual performance) is 73.12% while the average inverter performance (the ratio of the theoretical inverter efficiency to the actual inverter efficiency) is 98.56%. Moreover, it is found that the daily yield factor of the PV system is 2.51 kW h/kWp day while, the capacity factor is 10.47%. However, it is concluded that the productivity of the system is below the prospected rate and thus, an inspection of the system must be done in order to diagnose the problem of the system’s low productivity. This paper presents worthwhile information for those who are interested in PV system installation in Malaysia and nearby country.
  • Keywords
    Malaysia , Photovoltaic , Grid connected PV system
  • Journal title
    Energy Conversion and Management
  • Serial Year
    2013
  • Journal title
    Energy Conversion and Management
  • Record number

    2336822