Title of article :
Research on ration selection of mixed absorbent solution for membrane air-conditioning system
Author/Authors :
Li، نويسنده , , Xiuwei and Zhang، نويسنده , , Xiaosong and Wang، نويسنده , , Fang and Zhao، نويسنده , , Xiao and Zhang، نويسنده , , Zhuo، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2015
Abstract :
Absorption air-conditioning system is a good alternative to vapor compression system for developing low carbon society. To improve the performance of the traditional absorption system, the membrane air-conditioning system is configured and its COP can reach as high as 6. Mixed absorbents are potential for cost reduction of the membrane system while maintaining a high COP. On the purpose of finding ideal mixed absorbent groups, this paper makes analysis on COP, cost-effectiveness and economy of the membrane system with mixed LiBr–CaCl2 absorbent solution. The models of the system have been developed for the analysis. The results show the COP is higher for the absorbent groups with lower concentration of the total solute and higher concentration ratio of LiBr. It also reveals when the total solutes concentration is about 50%, it achieves the best cost-effectiveness and the economy. The process of the analysis provides a useful method for mixed absorbents selection.
Keywords :
MEMBRANE , Mixed absorbent , Air-conditioning , Performance
Journal title :
Energy Conversion and Management
Journal title :
Energy Conversion and Management