Investigation of pitting corrosion of a copper tube in a heating system
Author/Authors
Lee، نويسنده , , Seung-Hwan and Kim، نويسنده , , Jung-Gu and Koo، نويسنده , , Ja-Young، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2010
Pages
12
From page
1424
To page
1435
Abstract
Electrochemical tests, as well as surface and chemical analyses were used to examine the mechanism of pitting failure of a copper tube. Synthetic tap water simulating the hot water in a heating system and field-used heating water at 60 °C were used as electrolytes in these tests. The results showed that the presence of a Cu(I) oxide layer on the copper surface is essential for pitting corrosion of a copper tube in hot synthetic tap water. Moreover, the pitting corrosion of copper tubes is preferred in heating water containing higher concentrations of Fe species and under stagnant condition.
Keywords
Heating system , Electrochemical technique , Pitting corrosion , Copper tube