Title of article :
Demonstration of the operation and performance of a pressurised alkaline electrolyser operating in the hydrogen fuelling station in Porsgrunn, Norway
Author/Authors :
Kiaee، نويسنده , , Mahdi and Cruden، نويسنده , , Andrew and Chladek، نويسنده , , Petr and Infield، نويسنده , , David، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2015
Pages :
11
From page :
40
To page :
50
Abstract :
Operation of the hydrogen filling station at Herøya, Porsgrunn, Norway is reported and analysed in this paper. A 12 bar(g) pressurised alkaline electrolyser with a nominal load of 24 kW provides hydrogen for this filling station and is designed to work with time variable power from renewable resources. Two wind turbines rated at 6 kW each and two solar panels rated at 2.5 kW each are available on site to provide the power for hydrogen production which can then be used to supply a number of fuel cell and modified Internal Combustion Engine (ICE) vehicles. The station has a hydrogen storage capacity of 6.3 m3 in pressurised tanks at 450 bar(g). art of the authors’ experimental work, operational data and the characteristics of the pressurised alkaline electrolyser installed at the site under different operational modes have been collected and analysed. The archival value of this paper is the presentation and discussion of the electrolyser characteristics which are relevant to the identification of an acceptable control strategy to integrate such electrolyser loads within the power system and thus provide improved performance of the power system when exposed to the highly time variable energy supply from renewable sources.
Keywords :
operational performance , Hydrogen station , Electrical grid , Renewable power , Alkaline electrolyser
Journal title :
Energy Conversion and Management
Serial Year :
2015
Journal title :
Energy Conversion and Management
Record number :
2339344
Link To Document :
بازگشت