Abstract
An analysis of the catastrophic corrosion of the hot water pipeline system was made. The cause was oxygen, dissolved in water due to the malfunctioning of the degassing device in the water preparation phase. Because of differential aeration, cathodic and anodic areas formed underneath the oxide deposit on the bottom side of the pipeline. The consequence of the thus activated pitting corrosion was pipeline perforation. It is imperative to regularly test the water for dissolved oxygen and monitor its pH value.
Keywords
Hot water pipeline system , Water dissolved oxygen , Pitting corrosion , Differential aeration