Title of article :
The protective effect of a fire-retardant coating on the insulation failure of PVC cable
Author/Authors :
Wang، نويسنده , , Ji and Shu، نويسنده , , Zhongjun and Chen، نويسنده , , Zhen، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Pages :
9
From page :
1
To page :
9
Abstract :
The failure time of polyvinyl chloride (PVC) insulated power cables was studied using an infrared radiation heating furnace and insulation resistance measurements. The temperature–time curve inside the furnace was similar to that of the ISO 834 standard. Two popular fire protection methods were employed for the cables; one method applied fire-retardant coatings directly on the cable surface, and the other inserted the cables into metal conduits coated with structural steel fire-retardant coating. The results showed that for both protection methods, the failure time of the cable increased with the thickness of the coating. However, if the cable coatings were thicker than 1.5 mm, the coating will crack in the case of cable movement. When the steel structural coating was thinner than 1 mm or thicker than 3 mm, the protective effect was not remarkable for the relatively small expansion multiple. For the longest failure time of the cables, less than 10 min in these tests, neither of the two methods was effective in protecting the electrical cables that supply power (on transmit a signal) to equipment required to operate over a relatively long duration in fire conditions.
Keywords :
Fire retardant coating , Failure time , ISO 834 fire scenario , PVC insulated cable
Journal title :
Engineering Failure Analysis
Serial Year :
2013
Journal title :
Engineering Failure Analysis
Record number :
2339817
Link To Document :
بازگشت