• Title of article

    Failure of tube used in high pressure steam generator due to incrustation deposits

  • Author/Authors

    Tavares، نويسنده , , S.S.M. and Scandian، نويسنده , , C. and de Macêdo، نويسنده , , M.C.S. and Pardal، نويسنده , , J.M. and da Silva، نويسنده , , F.J.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2013
  • Pages
    8
  • From page
    25
  • To page
    32
  • Abstract
    In this work a failure analysis was conducted to investigate the premature failure of ASTM 106-Gr.B seamless tube used in steam generators. The failure occurred after 3 years of operation, due to a macroscopic crack with approximately 50 mm in the longitudinal direction. Incrustration deposits found in the region of failure were identified as sodium aluminum silicates (albite and nepheline). Micro-hardness profile showed a sharp increase of hardness near the crack, which was associated to microstructural changes observed by optical microscopy. Local over-heating of the tube has occurred due to the incrustation deposits. As a consequence, creep damage was produced and caused the crack of the tube. Temperatures in the austenitic field were achieved, since martensitic, bainitic and Widmansttنten ferrite structures were observed near the crack. In the crack tip, at the moment of leaking, the austenite underwent rapid cooling from the high temperature, producing hard microstructures in the crack neighborhood. Correct water treatment is recommended to avoid future failures in this type of tube.
  • Keywords
    Steam generator tube , Incrustation deposits , Creep , ASTM A-106 steel
  • Journal title
    Engineering Failure Analysis
  • Serial Year
    2013
  • Journal title
    Engineering Failure Analysis
  • Record number

    2339879