• Title of article

    Expert system for the assessment of power transformer insulation condition based on type-2 fuzzy logic systems

  • Author/Authors

    Flores، نويسنده , , Wilfredo C. and Mombello، نويسنده , , Enrique E. and Jardini، نويسنده , , José. A. and Rattل، نويسنده , , Giuseppe and Corvo، نويسنده , , Antonio M.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2011
  • Pages
    9
  • From page
    8119
  • To page
    8127
  • Abstract
    An efficient expert system for the power transformer condition assessment is presented in this paper. Through the application of Duval’s triangle and the method of the gas ratios a first assessment of the transformer condition is obtained in the form of a dissolved gas analysis (DGA) diagnosis according IEC 60599. As a second step, a knowledge mining procedure is performed, by conducting surveys whose results are fed into a first Type-2 Fuzzy Logic System (T2-FLS), in order to initially evaluate the condition of the equipment taking only the results of dissolved gas analysis into account. The output of this first T2-FLS is used as the input of a second T2-FLS, which additionally weighs up the condition of the paper-oil system. The output of this last T2-FLS is given in terms of words easily understandable by the maintenance personnel. The proposed assessing methodology has been validated for several cases of transformers in service.
  • Keywords
    Power Transformers , Type-2 fuzzy logic systems , Diagnostic reasoning , Knowledge-based systems , power transformer insulation
  • Journal title
    Expert Systems with Applications
  • Serial Year
    2011
  • Journal title
    Expert Systems with Applications
  • Record number