• Title of article

    Corrosion and activation analysis of the LIPAC beam dump cooling circuit

  • Author/Authors

    Parro، نويسنده , , M. and Karditsas، نويسنده , , P. and Caloutsis، نويسنده , , A. and Iglesias، نويسنده , , D. and Braٌas، نويسنده , , B. and Abلnades، نويسنده , , A.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2013
  • Pages
    4
  • From page
    827
  • To page
    830
  • Abstract
    The LIPAC beam dump cooling circuit has been modelled by means of TRACT (TRansport and ACTivation) code. TRACT simulates the flow and isotope transport inside a network of 1-D channels. The cooling circuit consists of the beam dump (inner cone and shroud made of EDP Cu (electrodeposited copper) and the cylinder made of SS304L), the piping from the cooling skid to the beam dump cell and the cooling skid itself composed of the heat exchanger, the purifying loop and the pump. Corrosion is an issue that deserves attention because of radioprotection reasons and because it could affect the cartridge thermomechanical performance. A simulation with TRACT for a water pH of 7 at the beam dump entrance has been performed, showing corrosion rates (< 1 g/(m2 year)) which do not compromise the beam dump performance.
  • Keywords
    tract , LIPAC , Beam dump , Corrosion
  • Journal title
    Fusion Engineering and Design
  • Serial Year
    2013
  • Journal title
    Fusion Engineering and Design
  • Record number