• Title of article

    Feasibility of using ground-coupled condensers in A/C systems

  • Author/Authors

    Said، نويسنده , , Syed Ahmad M. and Habib، نويسنده , , Mohamed A. and Mokheimer، نويسنده , , Esmail M.A. and El-Sharqawi، نويسنده , , Mostafa H.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2010
  • Pages
    4
  • From page
    201
  • To page
    204
  • Abstract
    The feasibility of using ground-coupled condensers for air-conditioning (A/C) systems in the Kingdom of Saudi Arabia has been investigated. Temperatures and soil properties required for the performance analysis of one of these condensers were determined experimentally. Thermal response tests were conducted to evaluate the effective thermal conductivity of the ground. The measurements required the installation of a closed loop vertical ground heat exchanger. The results indicated a significant difference between the ambient air and ground temperatures, which would result in an increase in the coefficient of performance and in a reduction in the energy consumption of an A/C unit using a vertical ground heat exchanger rather than an air-cooled condenser. The cost analysis indicated that the use of ground-source heat pumps in Saudi Arabia is not economical at the present time because of low electricity prices and high drilling costs.
  • Keywords
    Geothermal , Ground-coupled condensers , air-conditioning systems , Economic Feasibility , Saudi Arabia , Technical feasibility
  • Journal title
    Geothermics
  • Serial Year
    2010
  • Journal title
    Geothermics
  • Record number