Author/Authors :
Chaudhuri، نويسنده , , Subhasis and Singh، نويسنده , , Rajeev Kumar and Patwari، نويسنده , , Kuntal and Majumdar، نويسنده , , Susanta and Ray، نويسنده , , Asim Kumar and Singh، نويسنده , , Arun Kumar Prasad and Neogi، نويسنده , , Nirbhar، نويسنده ,
Abstract :
This paper describes a heat transfer model based automatic secondary cooling system for a billet caster. The model aims to minimize the variation in surface temperature and excessive reheating of the billet strands. It is also used to avoid the low ductility trough of the solidifying steel, which aggravates the tendency of steel to crack. The system has been designed and implemented in an integrated steel plant. A Programmable Logic Controller (PLC) based automation system has been developed to control the water flow in the secondary cooling zones of the strand. The results obtained through field trials have shown complete elimination of internal and off-corner cracks for the fifty billet samples that were monitored.
Keywords :
Billet caster , secondary cooling , Heat transfer equations , PLC