• Title of article

    COMPUTATION OF OPTIMUM PARAMETERS OF A HALF EFFECT WATER-LITHIUM BROMIDE VAPOUR ABSORPTION REFRIGERATION SYSTEM

  • Author/Authors

    Arora, Akhilesh Department of Mechanical Engineering - Delhi Technological University Delhi, Delhi, India , Dixit, Manoj Centre for Energy Studies - Indian Institute of Technology Delhi New Delhi, Delhi, India , Kaushik, S.C. Centre for Energy Studies - Indian Institute of Technology Delhi New Delhi, Delhi, India

  • Pages
    10
  • From page
    683
  • To page
    692
  • Abstract
    In this research paper, energy and exergy analyses of water lithium bromide half effect vapour absorption refrigeration system has been carried out. Based on energy and exergy analysis the optimum intermediate pressure is computed corresponding to maximum values of coefficient of performance and exergetic efficiency under various operating conditions. It is found that the optimum intermediate pressure corresponding to maximum values of coefficient of performance and exergetic efficiency is same. The effects of low and high pressure generator temperatures, evaporator temperature, effectiveness of solution heat exchangers and difference between low and high pressure generator temperatures have been considered in computing optimum intermediate pressure. The maximum COP varies between 0.415 - 0.438 and maximum exergetic efficiency varies between 6.96-13.74%.
  • Keywords
    Half effect , exergy analysis , Vapour Absorption Refrigeration , Water-lithium bromide
  • Journal title
    Journal of Thermal Engineering
  • Serial Year
    2016
  • Record number