Title of article :
THERMOECONOMIC ANALYSIS OF A WATER TO WATER HEAT PUMP UNDER DIFFERENT CONDENSER an‎d EVAPORATOR CONDITIONS
Author/Authors :
Aksu, B. TOBB Vocational School of Technical Sciences - Karabuk Uni., Karabuk, TURKEY , Uysal, C. TOBB Vocational School of Technical Sciences - Karabuk Uni., Karabuk, TURKEY
Pages :
12
From page :
198
To page :
209
Abstract :
A thermoeconomic analysis of a water to water heat pump are performed under different condenser and evaporator conditions. Experiments are realized for different volumetric inlet temperatures of 14.4, 17 and 19 °C and different volumetric flow rates of 50, 100, 150 lt/h for condenser cooling water. Same inlet temperatures with condenser cooling water are used for evaporator water inlet, while constant volumetric flow rate of 100 lt/h is used for each case. Modified Productive Structure Analysis (MOPSA) is used for thermoeconomic analysis. It is found that increases in inlet temperature and in volumetric flow rate cause to decrease in both the unit cost of heat delivered ( CH ) and the unit cost of entropy generation ( CS ). As a result, in the case of Tin =14.4 °C and ∀ = 50 lt/h, CH and CS values are obtained to be 0.0489 $/kWh and 0.0221 $/kWh, respectively, while CH and CS values are obtained to be 0.0385 $/kWh and 0.0175 $/kWh for Tin =19 °C and ∀ = 150 lt/h, respectively.
Keywords :
Water to Water Heat Pump , Condenser Cooling Water , Thermoeconomic Analysis , MOPSA
Journal title :
Journal of Thermal Engineering
Serial Year :
2019
Full Text URL :
Record number :
2582487
Link To Document :
بازگشت