• Title of article

    Experimental performance study of a proposed desiccant based air conditioning system

  • Author/Authors

    Bassuoni, M.M. Tanta University - Faculty of Engineering - Mechanical Power Engineering Department, Egypt

  • From page
    87
  • To page
    95
  • Abstract
    An experimental investigation on the performance of a proposed hybrid desiccant based air conditioning system referred as HDBAC is introduced in this paper. HDBAC is mainly consisted of a liquid desiccant dehumidification unit integrated with a vapor compression system (VCS). The VCS unit has a cooling capacity of 5.27 kW and uses 134a as refrigerant. Calcium chloride (CaCl2) solution is used as the working desiccant material. HDBAC system is used to serve low sensible heat factor applications. The effect of different parameters such as, process air flow rate, desiccant solution flow rate, evaporator box and condenser box solution temperatures, strong solution concentration and regeneration temperature on the performance of the system is studied. The performance of the system is evaluated using some parameters such as: the coefficient of performance (COPa), specific moisture removal and energy saving percentage. A remarkable increase of about 54% in the coefficient of performance of the proposed system over VCS with reheat is achieved. A maximum overall energy saving of about 46% is observed which emphasizes the use of the proposed system as an energy efficient air conditioning system.
  • Keywords
    Hybrid system , Dehumidification , Vapor compression system , Liquid , desiccant
  • Journal title
    Journal of Advanced Research
  • Journal title
    Journal of Advanced Research
  • Record number

    2589930