• Title of article

    Diagnostics of Oil Filled Cable Terminations

  • Author/Authors

    ADZMAN, MOHD RAFI Kolej Universiti Kejuruteraan Utara Malaysia - School of Electrical System Engineering, Malaysia , ISA, MUZAMIR Kolej Universiti Kejuruteraan Utara Malaysia - School of Electrical System Engineering, Malaysia , ISMAIL, BAHARUDDIN Kolej Universiti Kejuruteraan Utara Malaysia - School of Electrical System Engineering, Malaysia , LEHTONEN, MATTI TKK - Laboratory of Power System, Finland , HYVONEN, PETRI TKK - Laboratory of Power System, Finland

  • From page
    113
  • To page
    119
  • Abstract
    Cable termination is one of the important components in the electrical power system. A failure of it can cause a long interruption, costly repair and loss of revenue. An existing oil filled cable termination such as rubber tube and porcelain type of cable termination require an observation and preventive maintenance in order to prevent an enormous electrical system failure in future. One of the defects of this type of oil filled cable termination is the lack of insulation oil inside it. The worst case if it becomes totally empty and at the same time there is no approach that can help to detect it. This paper presents the work carried out to find any possible method that can be used to detect a drying out of oil impregnated paper tape cable terminations. Furthermore, the diagnosis has to be used without destroying the terminations. Two diagnosis methods; infrared (IR) thermography and X-ray imaging are reviewed and the diagnosis result is presented. By comparison of two diagnosis method in this work, the X-ray imaging method is the best approach to observe and detect a drying out of paper tape oil impregnated cable terminations.
  • Keywords
    IR Thermography , X , ray imaging , insulation and cable termination.
  • Journal title
    Journal of Engineering Research and Education
  • Journal title
    Journal of Engineering Research and Education
  • Record number

    2590371