Title of article
Predicting transformer temperature rise and loss of life in the presence of harmonic load currents
Author/Authors
Gouda, O.E. Cairo University - Faculty of Engineering - Electric Power and Mach, Egypt , Amer, G.M. Benha University - High Institute of Technology, Egypt , Salem, W.A.A. Benha University - High Institute of Technology, Egypt
From page
113
To page
121
Abstract
Power transformers represent the largest portion of capital investment in transmission and distribution substations. One of the most important parameters governing a transformer’s life expectancy is the hot spot temperature value. The aim of this paper is to introduce hot-spot and top-oil temperature model as top oil and hot spot temperature rise over ambient temperature model and thermal model under liner and non-linear loads. For more accurate temperature calculations, in this paper thermal dynamic model by MATLAB is used to calculate the power transformer temperature. The hot spot, top oil and loss life of power transformer under harmonics load are calculated. The measured temperatures of 25 MVA, 66/11 kV, ONAF cooling temperatures are compared with the suggested dynamic model.
Keywords
Hot spot temperature , Power transformer , Top oil , Thermal model
Journal title
Ain Shams Engineering Journal
Journal title
Ain Shams Engineering Journal
Record number
2648624
Link To Document