In this study, the year-round thermal performance of a qanat source
heat pump in supplying the required cooling and heating loads of a
case study building is investigated. Using TRNSYS software, dynamic
simulation of the proposed system is performed in three climate
zones including Hot/Dry, Cold/Dry, and Hot/Humid. The heat pump
and helical coil heat exchanger inside the qanat water are
mathematically modeled in MATLAB, and then, coupled to TRNSYS
model to evaluate the system transient performance. It is found that
the free energy ratio of the qanat source heat pump Hot/Dry climate
zone is on average 21.6% higher than compared to that of the air
source heat pump. In cold months, by increasing the temperature of
the inlet fluid to the helical coil heat exchanger inside the qanat, the
system coefficient of performance increases 15%. The increase of the
energy efficiency ratio of the system in the warm months is 7.7%. It is
also found the highest coefficient of performance and the lower
energy efficiency ratio of the system is obtained in the Hot/Humid
climate zone in comparison with the other zones; so that, the energy
efficiency ratio of the system in the Cold/Dry and Hot/Dry zones is
48% and 58% higher than that in the Hot/Humid zone, respectively.
The annual FER of 63.4%, 63.1%, 56.8%, and 53.3% are obtained in
Hot/Dry (Kerman), Cold/Dry (Mashhad), Hot/Dry (Tehran), and
Hot/Humid (Bandar Abbas), respectively. These findings suggest that
the building energy consumption significantly reduces using the
QSHP in all climatic conditions.