• Title of article

    Application of ANFIS Technique for Wide-Band Modeling of Overvoltage of Single-Conductor Overhead Lines with Arrester above Dispersive and Two-Layer Soils

  • Author/Authors

    Ostadzadeh ، Saeed Reza Faculty of Engineering - Arak University

  • From page
    241
  • To page
    254
  • Abstract
    In this paper, an efficient closed-form expression for overvoltage of overhead lines under direct strike in the presence of lightning arresters is presented. The lightning arresters are also grounded via two grounding systems namely vertical electrode and horizontal grid. The simulation results based on the exact method show that among different parameters, the resistivity of soil and line height affect the overvoltage. To extract the closed-form expression, adaptive-network-based fuzzy inference systems (ANFIS) are used. In creating the ANFIS-based expression, it is first assumed that the electrical parameters of the soil are constant. Then a number of input-output pairs (inputs are soil resistivity and line height and the output is overvoltage) are computed from exact methods to train the algorithm. Once the algorithm is converged, the efficient expression is extracted.This simple expression can be easily used in dispersive soils (frequency-variant electrical parameters) and horizontally two-layered soils (non-homogenous electrical parameters) provided that the equivalent frequency and equivalent resistivity concepts respectively in dispersive and two-layer soils are used.
  • Keywords
    Overhead line , arrester , dispersive , two , layer , overvoltage , ANFIS
  • Journal title
    AUT Journal of Electrical Engineering
  • Journal title
    AUT Journal of Electrical Engineering
  • Record number

    2773937