Title of article :
Watthour meter accuracy under controlled unbalanced harmonic voltage and current conditions
Author/Authors :
Domijan، نويسنده , , A.، نويسنده , , Jr.، نويسنده , , Embriz-Santander، نويسنده , , E.، نويسنده , , Gilani، نويسنده , , A.، نويسنده , , Lamer، نويسنده , , G.، نويسنده , , Stiles، نويسنده , , C.، نويسنده , , Williams، نويسنده , , C.W.، نويسنده , , Jr.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
9
From page :
64
To page :
72
Abstract :
This work presents the results of phase I of the project on the accuracy of watthour meters when subjected to closely-duplicated real-world unbalanced harmonic voltage and current conditions. Such real-world conditions involved differences in voltage and current magnitudes as well as differences in the voltage and current total harmonic distortion levels of each phase. Tests were performed on a selected sampte of nine three-phase and three single-phase watthour meters. Some results showed that under a particular set of unbalanced waveforms with harmonic conditions of I, > 80% ,aVnd > 2%, the percentage errors exhibited by these meters ranged from -10.09% to +O.52%.
Keywords :
watthour meter , Unbalance , power quality , Testing , field monitoring , waveform reproduction. , harmonics