Title of article :
Unsynchronized two-terminal fault location estimation
Author/Authors :
Novosel، نويسنده , , D.، نويسنده , , Hart، نويسنده , , D.G.، نويسنده , , Udren، نويسنده , , E.، نويسنده , , Garitty، نويسنده , , J.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Abstract :
A technique for fault location estimation which uses
data from both ends of the trmmksion line and which does
not require the data to be synchronized is d ~ ~ ~ b eThdetechnique fully utilizes the advantages of digital technology and
numerical relaying which are available today and can easily be
applied for off-line analysis. This technique allows for accurate
estimation of the fault location irrespective of the fault type,
fault resistance, load currents, and source impedances. Use of
two-terminal data allows the algorithm to eliminate previous
assumptions in fault location estimation, thus increasing the
accuracy of the estimate. The described scheme does not
require real time communications, only off-line post-fadt
analysis. The paper also presents fault analysis techniques
utilizing the additional communicated information.
Keywords :
Fault location , two-terminal fault location , Communications , Fault analysis , numerical relaying
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY