Abstract
V-t characteristics of spacer surfaces for VFT were
investigated under particle contaminated conditions. V-t
characteristics for VFT were measured with the particle length,
oscillation frequency, amplitude, and damping factor of VFT
waveform as parameters. Differences in V-t characteristics for VFT
due to variation of oscillation frequency, amplitude, and damping
factor were small. Further, they were compared with V-t
characteristics for lightning impulse. The dielectric strength of
spacer surfaces for VFT was found to be at least equivalent to the
dielectric strength for lightning impulse.