Title of article
BPAʹs Pacific AC intertie series capacitors: experience, equipment and protection
Author/Authors
Lee، نويسنده , , G.E.، نويسنده , , Goldsworthy، نويسنده , , D.L.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
7
From page
253
To page
259
Abstract
Over BPAʹs 40 years of series capacitor
experience, equipment evolution has dramatically reduced
the complexity of capacitor protection systems. BPA and
other utilities in the Pacific Northwest recently installed 13
new metal oxide varistor (MOV) protected series
capacitors. Nearly all the banks use a simplified design
which eliminates the typical triggered gap bypass
protection for the MOV. The decision to use a gapless
design, the MOV energy sizing, and the protective bypass
thresholds require extensive EMTP fault simulations. A
large number of staged system fault tests were performed
to evaluate the integrity of the banks.
Keywords
MOV , EMTP , Varistor , Series compensation , Transient Simulations , Fault Tests. , Series Capacitors