Title of article
Observation and analysis of multiple-phase grounding faults caused by lightning
Author/Authors
Inoue، نويسنده , , A.، نويسنده , , Kanao، نويسنده , , S.-I.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
8
From page
353
To page
360
Abstract
his paper describes four-phase and five-phase grounding faults
caused by lightning on a 154-kV overhead transmission line. The authors
measured insulator voltages and currents flowing along the ground wire
and the tower. In addition, they photographed lightning strokes to the
transmission line and flashovers between the arcing horns and examined
the fault phases at substations. The paper analyzes insulator voltage
waveforms using the Electromagnetic Transients Program (EMTP) and
estimates the fault processes.