  • Abstract
    500-kV XLPE-insulated cable with an insulation thickness of 27 nun has been developed for longdistance transmission lines. Basic studies ion 500-kV XLPE cable have shown that contaminants in the insulation may be the factor determining electrical performance, This hypothesis is justified by the good correlation obtained between statistical estimations of the size of the largest contaminant in the insulation and the electrical characteristics of full-sized cables. Voltage-withstand and long-term tests have confirmed the design values for minimum breakdown stress, for AC and impulse voltage, and for the degradatioin coefficients.
  • Keywords
    500 kV , XLPE cable , minimum insulation breakdown strength , designstress , performance-determiningfactor