Title of article
Development of 500-kV XLPE cables and accessories for long distance underground transmission line. III. Electrical properties of 500-kV cables
Author/Authors
Fukawa، نويسنده , , M.، نويسنده , , Kawai، نويسنده , , T.، نويسنده , , Okano، نويسنده , , Y.، نويسنده , , Sakuma، نويسنده , , S.، نويسنده , , Asai، نويسنده , , S.، نويسنده , , Yoshihide Kanaoka، نويسنده , , M.، نويسنده , , Yamanouchi، نويسنده , , H.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
8
From page
627
To page
634
Abstract
500-kV XLPE-insulated cable with an insulation
thickness of 27 nun has been developed for longdistance
transmission lines. Basic studies ion 500-kV
XLPE cable have shown that contaminants in the insulation
may be the factor determining electrical performance,
This hypothesis is justified by the good correlation
obtained between statistical estimations of the
size of the largest contaminant in the insulation and
the electrical characteristics of full-sized cables.
Voltage-withstand and long-term tests have confirmed
the design values for minimum breakdown stress, for AC
and impulse voltage, and for the degradatioin coefficients.
Keywords
500 kV , XLPE cable , minimum insulation breakdown strength , designstress , performance-determiningfactor