Title of article
Anatomy of power system blackouts: preventive relaying strategies
Author/Authors
Tamronglak، نويسنده , , S.، نويسنده , , Horowitz، نويسنده , , S.H.، نويسنده , , Phadke، نويسنده , , A.G.، نويسنده , , Thorp، نويسنده , , J.S.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
8
From page
708
To page
715
Abstract
Major blackouts of electric power systems in
which many customers are left without power are rare events.
However, the effects of blackouts, for instance, can be
catastrophic. It has been observed that protective system
failures are a contributing factor in a large proportion of these
blackouts. The most troublesome protection system failures
are hidden failures, which remain dormant during normal
system conditions, and are exposed during system
disturbances. A study of hidden failures of the protective
systems is undertaken to uncover their modes of failures, and
to determine means of supervising their actions in times of
highly stressed power system operations. The main
contribution of this paper is to develop and document a
method of quantitative analysis of the si@cance of hidden
failures of protection systems. A complete protection system
was designed for the New England 3 9 - b ~sy stem and the
hidden failure modes were used to develop regions of
vulnerability and a vulnerability index. Through this analysis,
critical protection systems, whose hidden failures would have
a major impact on cascading failures or blackouts of the
power system, can be idenufied. These protection systems are
candidates for increased monitoring and control, which would
help alleviate the problems posed by hidden failures.
Keywords
blackouts , computer relaying , regions of vulnerability , hidden failures , adaptive relaying
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1996
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399119
Link To Document