Title of article
A fast and accurate analysis of grounding resistance of a driven rodbed in a two-layer soil
Author/Authors
Elsherbiny، نويسنده , , M.M.، نويسنده , , Chow، نويسنده , , Y.L.، نويسنده , , Salama، نويسنده , , M.M.A.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
7
From page
808
To page
814
Abstract
A moment method of the Galerkin (variational) approach is applied
to analyze the grounding resistances of driven rodbed of various
configurations. Using this approach the resistance of a rodbed of N
rods in two-layer soil requires only a mauix size of 2NX2N (two
segments for each rod). The error m the calculated resistance is less
than 4% compared to the resistance calculated by point matching
moment method of large number of segmentation for each rod. The
efficiency due to a small maw with high accuracy allows an
extensive parametric analysis of the rodbed. The study shows that a
precise placement of the rods is not necessary to maintain a given
resistance.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1996
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399130
Link To Document