• Title of article

    A fast and accurate analysis of grounding resistance of a driven rodbed in a two-layer soil

  • Author/Authors

    Elsherbiny، نويسنده , , M.M.، نويسنده , , Chow، نويسنده , , Y.L.، نويسنده , , Salama، نويسنده , , M.M.A.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1996
  • Pages
    7
  • From page
    808
  • To page
    814
  • Abstract
    A moment method of the Galerkin (variational) approach is applied to analyze the grounding resistances of driven rodbed of various configurations. Using this approach the resistance of a rodbed of N rods in two-layer soil requires only a mauix size of 2NX2N (two segments for each rod). The error m the calculated resistance is less than 4% compared to the resistance calculated by point matching moment method of large number of segmentation for each rod. The efficiency due to a small maw with high accuracy allows an extensive parametric analysis of the rodbed. The study shows that a precise placement of the rods is not necessary to maintain a given resistance.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1996
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399130