Suppression of VFT in 1100 kV GIS by adopting resistor-fitted disconnector
Author/Authors
Yamagata، نويسنده , , Y.، نويسنده , , Tanaka، نويسنده , , K.، نويسنده , , Nishiwaki، نويسنده , , S.، نويسنده , , Takahashi، نويسنده , , N.، نويسنده , , Kokumai، نويسنده , , T.، نويسنده , , Miwa، نويسنده , , I.، نويسنده , , Komukai، نويسنده , , T.، نويسنده , , Imai، نويسنده , , K.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
9
From page
872
To page
880
Abstract
With lOOOkV transmission lines planned in Japan,
very fast transient (VFT) phenomena will be suppressed
by installing a resistor in a disconnector Of gas insulated
switchgear (GIs). In this paper the VFT overvoltage suppressing
effect of the resistor and the duty required of the resistor
are clarified. A llOOkV resistor-fitted disconnector was tested
by constructing a charging current interruption test circuit. It
has been clarified that the disconnector accepts the required
duty. The disconnector tested here will be used for the field
test.