Title of article :
Analysis of internal winding stresses in EHV generator step-up transformer failures
Author/Authors :
Morched، نويسنده , , A.S.، نويسنده , , Marti، نويسنده , , L.، نويسنده , , Brierley، نويسنده , , R.H.، نويسنده , , Lackey، نويسنده , , J.G.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
7
From page :
888
To page :
894
Abstract :
This paper descrjbes studies carried out to investigate the failure of one phase of a 990 MVA generator step-up transformer bank at one of Ontario Hydroʹs major generating stations. A high accuracy frequency dependent transformer model was used to determine the behaviour of the transformer at the terminals under transient conditions. With this information, and with measured transfer functions between the terminals and various points inside the windings, it was possible to create internal voltage distribution maps. This information was then used to evaluate the insulation stresses within the winding, and to ascertain that the use of additional capacitance at the HV terminals to reduce the magnitude and frequency of incoming transients would be adequate to reduce the disk-to-disk stresses near the line end of the HV winding. The values of the HV terminal capacitances were chosen so that no undue stresses in other portions of the winding would take place.
Keywords :
Transformer Internal Resonances , Winding Transfer Functions , EMTP. , Transformer Failure
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1996
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399140
Link To Document :
بازگشت