• Title of article

    Thyristor controlled ground fault current limiting system for ungrounded power distribution systems

  • Author/Authors

    Sugimoto، نويسنده , , S.، نويسنده , , Neo، نويسنده , , S.، نويسنده , , Arita، نويسنده , , H.، نويسنده , , Kida، نويسنده , , J.، نويسنده , , Matsui، نويسنده , , Y.، نويسنده , , Yamagiwa، نويسنده , , T.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1996
  • Pages
    6
  • From page
    940
  • To page
    945
  • Abstract
    A thyristor controlled ground fault current limiting system (TGCL) was proposed to prevent one-line ground fault current rises due to increased capacitance to ground. Basic components of the TGCL are a main ground fault current limiter, which rapidly adjusts a compensating reactor level for the capacitance to ground, and the TGCLʹs controller. Control is ensured by an in-phase control method for zero-phase sequence voltage and current. The method determines the direction of ground faults and the compensating reactor level. The fast control which can be realized shows the TGCL is a valuable protecting system for high ground fault current distribution systems.
  • Keywords
    Ground Fault , Current Limiter , Thyristor Control , FaultProtection , Distribution System.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1996
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399147