Title of article :
Electric shock and elevated EMF levels due to triplen harmonics
Author/Authors :
Tran، نويسنده , , T.Q.، نويسنده , , Conrad، نويسنده , , L.E.، نويسنده , , Stallman، نويسنده , , B.K.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
9
From page :
1041
To page :
1049
Abstract :
The increasing use of single phase rectifiers for electric power conversion in residential applications increases harmonic load on utility systems. Many papers have analyzed the effect of these loads on power quality and equipment loadability. However there are two more critical concerns for harmonic loads served phase to neutral on multi-grounded wye systems. Triplen harmonics, particularly the third, add in the neutral and have little diversity between loads. The higher neutral currents may cause significant problems. Neutral to earth voltages will increase near the substations which could increase stray voltage complaints. The additional neutral current on three phase lines will elevate EMF levels especially in the fringe areas, This paper provides fundamental understanding of triplen harmonic influence on stray voltage and EMF related to multi-grounded wye electric distribution systems.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1996
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399158
Link To Document :
بازگشت