An application study for sizing and rating controlled and conventional series compensation
Author/Authors :
Kosterev، نويسنده , , D.N.، نويسنده , , Mittelstadt، نويسنده , , W.A.، نويسنده , , Mohler، نويسنده , , R.R.، نويسنده , , Kolodziej، نويسنده , , W.J.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
7
From page :
1105
To page :
1111
Abstract :
A step by step method for determining controlled and conventional series compensation requirements is developed. The Montana 500kV transmission system is taken as an example in this study. A base transfer rating of 2200MW for the system already exists, and it is assumed that as its power loading increases, controlled series compensation is needed to reinforce the system. Combination of conventional and thyristor-controlled series compensators (TCSCs) is considered as a means of increasing the system transfer capability. Powerflow and transient stability studies are performed to rate and size the series compensators. The TCSC reactance control capabilities are established for steady-state and transient conditions. An installation sequence is developed relating facility requirements to system loading.
Keywords :
transmission system planning , FACTS. , Series Capacitors , thyristor-controlled seriescompensation