Title of article :
Calculation of single phase AC and monopolar DC hybrid corona effects
Author/Authors :
Zhao، نويسنده , , T.، نويسنده , , Sebo، نويسنده , , S.A.، نويسنده , , Kasten، نويسنده , , D.G.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Abstract :
Operating a hybrid HVac and HVdc line is an
option for increasing the efficiency of power transmission and
overcoming the difficulties in obtaining a new right-of-way.
This paper proposes a new calculation method for the study
of hybrid line corona. The proposed method can be used to
calculate dc corona losses and corona currents in dc or ac
conductors for single phase ac and monopolar dc hybrid lines.
Profiles of electric field strength and ion current density at
ground level can be estimated. The effects of the presence
of an energized ac conductor on dc conductor corona and dc
voltage on ac conductor corona are included in the method.
Full-scale and reduced-scale experiments were utilized to investigate
the hybrid line corona effects. Verification of the
proposed calculation method is given.
Keywords :
Hybrid lines , electric fieldstrength , corona current computation , ion current density , reduced-scale modeling. , Corona current
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY