Title of article :
Reduction of audible noise using asymmetrical bundles for 1000 kV transmission lines: full-scale test results of Akagi test line
Author/Authors :
Tanabe، نويسنده , , K.، نويسنده , , Takebe، نويسنده , , T.، نويسنده , , Isozaki، نويسنده , , M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Abstract :
Long-term tests of asymmetrical bundles
which have the potential to suppress corona activity on
conductor bundles have been carried out in the Akagi
test line. and their corona performance. mainly audible
noise, was measured. Asymmetrical bundles
generally show good performance; however, the "added
system", which is classified as an asymmetrical bundle
due to the addition of a subconductor at the bottom
of regular symmetrical conductor bundles. shows
better performance. These reduction techniques
can be applied to actual 1000 kV transmission lines
because of their good corona-suppressing performance,
if problems such as mechanical performance
and unbalanced current passing through individual
subconductors can be resolved.