Title of article :
Very high frequency overvoltages at open air EHV substations during disconnect switch operations
Author/Authors :
Rashkes، نويسنده , , V.S.، نويسنده , , Ziles، نويسنده , , L.D.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Abstract :
EHV open air substations experience flashovers
produced by very high frequency overvoltages (VHF OV) during
disconnect switch operations. It was found during field tests that
the highest measured value of sparkover voltage across the EHV
switch gap between contacts during its operation was 1.9 p.u. The
most unfavourable scheme, theoretically, occurs when a bus is fed
from a single transformer, without outgoing lines. Calculations
showed that in 787 and 525 kV substations with branched buses
VHF OV could result in flashovers on a bus open end with
unfavourable ratio of bus lengths. For transformer insulation
protected with an arrester VHF OV are not dangerous. Some
protective measures are recommended.
Keywords :
Overvoltage- Very High Frequency- Extra HighVoltage.