Author/Authors :
Novosel، نويسنده , , D.، نويسنده , , Bachmann، نويسنده , , B.، نويسنده , , Hart، نويسنده , , D.، نويسنده , , Yi Hu، نويسنده , , Saha، نويسنده , , M.M.، نويسنده ,
Abstract :
This paper investigates a scheme to improve the
reach measurement of distance relays and fault locators for
series compensated lines. A deterministic method and a
feedforward neural network method have been implemented
for on-line calculation of the voltage across a non-linear
capacitor installation. These techniques are compared and
incorporated into a new relaying scheme which is independent
of the series capacitor installation, operation of the capacitor
protection, and the surrounding power system elements. The
proposed scheme is simple and accurate and requires only
local voltage and current at the bus. Detailed testing using
EMTP has been done to show the benefits of the new adaptive
scheme. The results demonstrate the suitability of the
techniques for real world applications.