• Title of article

    Verification of measured transmission system phase angles

  • Author/Authors

    Wilson، نويسنده , , R.E.، نويسنده , , Sterlina، نويسنده , , P.S.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1996
  • Pages
    5
  • From page
    1743
  • To page
    1747
  • Abstract
    Measurement of power system phase angle is being studied for use in protective relaying, critical control circuits, and other applications. This paper compares phase angles measured by a synchronized measuring unit during field testing with classical theory. Power system positive sequence voltage and current phasors were recorded during testing of a new 525 kV compensated transmission system. Steady-state phase angles (6) and magnitudes were measured relative to a satellitebased global time standard on synchronized measurement units at two substations. Phase angles were calculated using recorded supervisory system and sending-end values of total power flow. Field measurements of the phase angle across a transmission system differed from calculations by -0.09" on the average, contributing to verification of the new synchronized measurement technique.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1996
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399250