Title of article :
Ampacity of cables in single covered trays
Author/Authors :
Harshe، نويسنده , , B.L.، نويسنده , , Black، نويسنده , , W.Z.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1997
Abstract :
A mathematical thermal model is developed
to predict the operating temperatures of cables in a single
covered tray when there is load diversity in the cable
bundle. The model accommodates two different loading
scenarios - one in which the heat is distributed evenly
across the cable tray cross section and the second one
which concentrates the heavily loaded cables along the
centerline, while surrounding them with more lightly
loaded cables. The temperature predictions provided by
the model are compared to data found in other IEEE
papers, data collected in laboratory measurements, and
new data from a four-year study of cable trays in an
operating nuclear plant. Reasons for differences between
the field data and the computer results are discussed. The
model is used to evaluate the conservatism in the available
Codes and Standards.
A derating factor is introduced that is defined in terms
of the ampacity of cables in open-top trays. The derating
factor accounts for the added thermal resistance present
when a cover is placed over the cables, trapping a layer of
stagnant air on top .of the cable mass. The computer
model is then used to predict values for the derating
factor as a function of cable depth. The derating factor
is shown to be independent of the composition of cables in
the tray. The presence of a cover is shown to reduce the
ampacity based on an uncovered tray by up to 25 percent
depending on the depth of the cables in the tray.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY