This paper reports on distance relay application
testing using simulated transient waveforms. Power system
modeling and test procedure for using modern digital simulators
are presented. Extensive study of five commercial relays
comparing the application for a 345kV transmission line is
carried out by performing thousands of oneterminal and
synchronized two-terminal transient tests. The approach using
digital simulators has proved to be an efficient technique. This
paper presents a methodology for evaluating distance relay
transient performance based on extensive laboratory testing.
Important issues regarding application testing, such as CT and
CCVT effects and selection of prefault waveform length, are
also addressed and investigated in this paper.