Current transformer (CT) saturation may cause
relays to malfunction. The conventional method to deal with
the problem is overdimensioning of the core so that CTs can
carry up to 20 times the rated current without exceeding 10 ʹ/a
ratio correction. However, this not only reduces the sensitivity
of relays, but also increases the CT core size. This paper
presents a technique of estimating the secondary current
corresponding to the CT ratio under CT saturation. The
proposed algorithm can improve the sensitivity of relays to low
level internal faults, minimize the instability of relays for
external faults, and might ultimately assist in reducing the
dimension of the required CT core cross section.