• Title of article

    High voltage VLF testing of power cables

  • Author/Authors

    Eager، نويسنده , , G.S.  Katz، نويسنده , , C.  Fryszczyn، نويسنده , , B.  Densley، نويسنده , , J.  Bernstein، نويسنده , , B.S. ، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1997
  • Pages
    6
  • From page
    565
  • To page
    570
  • Abstract
    This publication describes a laboratory test program conducted with the objective to develop a test that would replace the existing dc withstand test. The article describes the methodology used to establish the voltage duratlon and magnitude of VLF (0.1 Hz) high voltage field tests suitable for crosslinked polyethylene @WE) Insulated power cable. The results show that the voltage breakdown of laboratory aged XLPE cable at 0.1 Hz Is approximately equal to that at 60 Hz, that proof tests at 0.1 Hz cause very little damage to the cable, and that 0.1 Hz testing appears to be a satisfadory alternate to dc testing. Preliminary values are SUggeStQd for voltage magnitude and time duration of cable acceptance, main-tenance and proof tests at 0.1 Hz for XLPE cable ratad up to 35 kV. A program is underway to similarly evaluate samples of serviceaged XLPE cable; as well as to demonstrate the use of the preliminary test values at typical utility installations.
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1997
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399360