Title of article :
A distributed on-line HV transmission condition monitoring information system
Author/Authors :
Chan، نويسنده , , W.L. Pang، نويسنده , , S.L. Chan، نويسنده , , T.M. So، نويسنده , , A.T.P.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1997
Abstract :
China Light & Power Company Ltd. (CLP)
is responsible for supplyingelectricity to the whole of Hong
Kong except Hong Kong Island and Lamma Island. In
CLPʹs Castle Peak power plant, 18 kV and 23 kV electric
supplies are generated. The voltage is then stepped up to
400 kV for transmission. The intermediate control between
those transformers and the major 400 kV overhead
transmission system lies with a standard "One and a half
Breaker Configuration" switch substation. The substation
houses single phase encapsulated SF, circuit breakers. In
the urban centres, 400 kV substations are installed to step
down 400 kV to 132 kV or further to 11 kV for
distribution. This paper describes the development of a online
distributed information system for monitoring the
conditions of the whole HV transmission system. The
system continuously monitors status of each circuit breaker
(CB) together with important operational parameters, such
as duration during making and breaking, operations of
hydraulic pumps and SF, gas pressure etc. Each group of
CBs is monitored by a standalone microcontroller which is
interconnected with all other microcontrollers using a local
area network with a baud rate of 9,600. The information
can be recorded on the harddisk of an on-site
microcomputer and further transmitted back to a remote
computer for alarm generation and multi-station
supervision. The CLP 400 kV substation and the Tsz Wan
Shan 400 kV substation are amongst the first targets for
development.