Abstract
Pollution test results of single unit 110 kV metal
oxide surge arresters with porcelain housing according to the
solid layer and salt fog methods are presented. During 6 hours
of testing, the internal and external charge and maximum
temperature along the varistor column were measured. The
formation of single stable dry bands on the housing was often
observed, especially during salt fog tests. In such cases, the
varistor temperature can reach about 70°C. The simple
electrical model of the arrester enabling calculations of
voltages and currents as a function of arrester and pollution
parameters is shown.