A control device for point-on-wave closing or autoreclosing
of shunt reactor compensated transmission lines for
reduction of closing overvoltages is presented. The device is the
first of its kind. It was put into field service successfully more
than a year ago. Development aspects and basic investigations
on the relevant transient switching phenomena are presented.
The algorithm employed works independently of the shape of
the voltage signal to be synchronized on by means of pattern
recognition. Peculiarities of the hardware are high redundancy
and a system to bypass the controller at any malfunction of the
electronic circuits. The efficiency of the controller was verified
by a combination of transient network analyser tests and
EMTP simulations showing the ability of the device to suppress
overvoltages. This procedure is generally recommended for
future application of control devices as a type test procedure.