Title of article :
Transmission line corona losses under hoar frost conditions
Author/Authors :
Lahti، نويسنده , , K. Lahtinen، نويسنده , , M. Nousiainen، نويسنده , , K. ، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1997
Abstract :
Power transmission line corona losses under hoar frost conditions were studied in the climate room of the high voltage laboratory of Tampere University of Technology, Finland. The measurements were performed using a coaxial measurement arrangement with different bundle and conductor types. The effects of conductor and bundle type, temperature, applied voltage and hoar frost thickness on corona losses were investigated. A two-conductor bundle had corona losses about 2.5...5 times higher than a three-conductor bundle. Relatively thin hoar frosts were used in the tests. Even the thinnest hoar frost resulted in remarkable corona losses and the losses were very sensitive to changes in the hoar frost thickness. The ambient temperature had a strong influence on the measured losses
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY